48V 160A Lithium Ion Battery Charger for Lithium Ion, Lead Acid, AGM & Gel Batteries

SKU: CXC48160 Weight: 160 lbs

Quantity

Product Details

OUTPUT POWER RATINGS
Voltage: 58.4V (customizable)
Amperage: 160A DC

PHYSICAL SPECIFICATIONS
25.3" L
29.1" H
24.7" W
160 lbs. 

TECHNICAL DATA
● Single-phase input voltage 208/240/480 VAC - Frequency 50/60 Hz.
● Three-phase input voltage 208/240/480/600 VAC - Frequency 50/60 Hz.
● Transformer adjustments to ±5% VAC.
● Tropicalized stray-flux transformer, copper windings with double enamel
insulation, class H, impregnated with non-toxic resins, kiln-dried.
● Transformer with UL recognized insulation system which ensures high
reliability even in heavy-duty conditions.
● Low voltage control circuit (24 VAC).
● Overload cutout on transformer.
● Rectifier bridge equipped with interference suppressing filters.
● Protection fuses on mains input, auxiliary circuits and D.C. output.
● Final acceptance test performed in compliance with UL, CSA, CE/ TÜV
safety requirements.
● Complete with battery cables and connector.
● Power cord to be installed by the customer.
● Electronic controller AP735USA with microprocessor and failure
diagnostics powered from battery voltage.
● Polycarbonate panel with LED’s indicating the charging stages.
● Charger switching off on battery disconnection while on charge.
● LED’s indicating charging stages or faults, if any.
● 4 digit LCD with 12 multifunctional symbols displaying the charging data
recalled by pushing the ON-OFF button.
● Charger complies with FCC and CE/TÜV rules and requirements on
Electromagnetic Compatibility.

TL EQUALIZER CHARGING CHARACTERISTIC 

● Charging with decreasing current until a voltage of 2.40 V/cell is reached
and the gas charging stage begins (adjustable).
● Time-controlled gas charging stage, adjustable by DIP switches
(3 hours as standard).
● Foreseen charging time: 9 ÷10 hours (without equalizing charge).
● The equalizing charge is automatically performed 60 minutes after the last
charge cycle. It is performed during the night and is repeated once a week
as maintenance cycle.

MATIC POINT / POWER POINT CHARGING CHARACTERISTIC

● Charging with decreasing current until a voltage of 2.40 V/cell is reached
and the gas charging stage begins (adjustable).
● Ah and dV/dt controlled gas charging stage available to optimize the
overcharging factor, making it independent of mains fluctuations, battery
discharge factor and status, thus ensuring a longer battery life.
● Time-controlled gas charging stage as an alternative adjustable by DIP
switches (3 hours as standard).
● Foreseen charging time: 9 ÷10 hours (without equalizing charge).
● The equalizing charge is automatically performed 60 minutes after the last
charge cycle. It is performed during the night and is repeated once a week
as maintenance cycle.

LCD DISPLAYING CHARGING DATA

● Real Time Delivered Current (A)
and Battery Voltage (V)
● Battery Voltage before charging (V)
and Initial Current of the Charge (A)
● Delivered Charge (Ah)
● Overall charging time (hours : minutes)
● Final Voltage reached by battery (V)
and Final Current delivered (A)

The following charging parameters can be programmed
by means of DIP switches:
1. Automatic start (Autostart)
2. Final charge timer settable from 1h to 5h 30m
3. Safety timer on the initial stage settable to 7h or 11h
(standard)
4. Equalizing charge
5. Proportional charge